70 DW SERIES
MULTIPARAMETRIC CONTROLLER FOR DRINKING WATER TREATMENT
The 70DW Series is a cutting-edge controller offering simultaneous display of as many of eight measurements for the monitoring and management of primary and drinking water plants.
The 70DW Series’ intuitive interface simplifies measurement calibration and setting of dosing parameters and, in the absence of flow, a dedicated digital input immediately ceases dosing and sends a signal via an alarm relay.
FEATURES
- 7" RGB 800x480 colour display
- Displays up to 8 measurements simultaneously
- Readings saved in internal data logger
- Stored data downloadable via integrated Wi-Fi module or USB.
- Up to 8 mA outputs available for proportional dosing
- Modbus RS485 serial protocol
- 8 relays
MEASURES
- Conductivity
- Free chlorine
- ORP
- pH
- Temperature
- Turbidity
- Analogue input (4-20 mA) freely programmable
TECHNICAL SPECIFICATION
Feature | DESCRIPTIOn |
---|---|
Display | 7" TFT LCD graphic colour display 800x480 RGB with resistive touch 16:9 |
Languages | Italian, English, French, German, Spanish |
Data Logger | Internal Flash 64Mbit. Download by USB port or Wi-Fi |
Recording Method | Circular (F.I.F.O.) or filling |
Display of Stored Data | In tabular and graphical form with indication of maximum, minimum and average values of the period recorded; Zoom function |
PID Control | Settable functions: P [Proportional]; PI [Proportional – Integral]; PID [Proportional – Integral – Derivative] |
Activation | On analogue or digital output |
Proportional Range | 0...500% |
Time Integral and/or Derivative | 0:00...5:00 min |
Analogue Outputs | Eight programmable; 0/4...20 mA; galvanic separation; opto-isolator 1KV; maximum load 500 Ohm |
Digital Outputs | Eight freely programmable; 1A 230V ON-OFF or PWM function |
Alarm Output | NAMUR; 3.6 mA [with range 4...20 mA] |
Alarm/Wash | Two alarms: instrument fault, minimum/maximum value, delay set point delay (live check); Washing: programming of the interval (minimum 15 minutes) and duration from 00:00...24:00 hh:mm |
Digital Inputs | Two for dosage disabling or washing cycle activation |
Input Voltage | 24 Vdc/ac |
Absorption | 10mA max |
Serial Outputs/Ports | Programmable RS485 for setup and remote real-time data or stored data download |
Baud Rate | 1200...38400 |
Manual Commands | Simulation of all analogue and digital outputs via keyboard |
Power Supply | 90 - 240 Vac/dc 47 - 63 Hz |
Transformer Isolation | 4 kV |
Power Consumption | ≤ 20W |
Electrical Protection | EMI/RFI CEI-EN55011 - 05/99 |
Mounting | Wall |
Container | Red ABS |
Dimensions (WxHxD) | 250x160x116 mm |
Mechanical Protection | IP66 |
Weight | 1 kg |
Operating Temperature | 0...50°C |
Humidity | 10...95% non-condensing |
Storage and Transport | -25...65°C |